10ft

Containerized Hybrid System

  1. Home
  2. »
  3. Products
  4. »
  5. 5MWh Pre-made Energy Storage Cabin

Product Features

  • Achieves up to 500kW / 1044kWh within a 10ft container.

  • Enables direct PV coupling, minimizing energy conversion losses.
  • Maintains peak performance across diverse climates.

  • Pre-integrated unit, ready for operation upon commissioning.

System Technical Specifications

Product Model250kW/522kWh375kW/783kWh500kW/1044kWh125kW/522kWh250kW/1044kWh
Battery Parameters
Single Battery SpecificationsLFP 314Ah    
Battery System Capacity (kWh)52278310445221044
Battery Pack Series and Parallel Connection Methods1P52S
String Formation2P260S3P260S4P260S2P260S4P260S
Rated Operational Voltage (V)832
Operating Voltage Range (V)728~923    
Rated Discharge Rate of Electricity (C)0.50.25
Photovoltaic Side Parameters     
Maximum Input Power (kW)5007501000250500
Maximum Input Voltage (V)1000
Rated Input Voltage (V)600
Starting Voltage (V)180
MPPT Voltage Range (V)150~950    
Maximum Input Current of Photovoltaic System  (V)20*4230*4240*4210*4220*42
Maximum Input Short-circuit Current of Photovoltaic (V)20*6030*6040*6010*6020*60
MPPT Quantity/Maximum No. of Input String Circuits20/4030/6040/804631520/40
Grid output parameters
Output Rating (kW)250375500125250
Maximum Output Apparent Power(kVA)250375500125250
Rated Grid Voltage (V)3/N/PE,230/400
Rated Grid Frequency (Hz)50/60
Grid Input Parameters     
Maximum Input Current (A)5007501000250500
Off-Grid AC Output Parameters     
Output Rating (kW)250375500125250
Maximum Output Apparent Power (kVA)250375500125250
Rated Grid Voltage (V)3/N/PE,230/400
Rated Grid Frequency (Hz)50/60
Off-Grid Switching Time (ms)<20
Generator Input Parameters     
Maximum Input Power (kW)250375500125250
Rated Input Voltage(V)3/N/PE,230/400
Rated Input Frequency (Hz)50/60
System Parameters
Container Protection GradeIP54/IP55
Dimensions of the single battery compartment(W*D*H,mm)2991*2438*2896
Battery System Cooling MethodLiquid cooling
Hybrid Inverter Cooling MethodWind cooling
Operating Temperature (℃)-20~55
Operating Humidity5%~95%RH(No condensation)
Working Altitude(m)≤3000 (>2000m needs decentralization)
Fire Fighting MediumTemperature sensation + smoke sensation + combustible gas detection + ventilation + aerosol + water spray
Communication InterfaceEthernet/CAN/485
Reference Weight (t)≈7.5≈9.5≈11.5≈7≈11